Important
All EMP protectors of the following series are supplied with properly installed GDT.
EMP protectors with replaceable GDT
The suitable replacement GDT is shown on the data sheet of the protector.
EMP protectors with fix installed GDT (no replacement possible)
Non-ionized GDTs
For first selection and replacement of size 6x8 mm GDT
Suitable for the following installed GDT holders:

| H+S Type |
UZstat (V) |
UZdyn (V) |
IS 8/20 µs (kA) |
ISG 8/20 µs (kA) |
UARC (V) |
Dim. (mm) |
|||||||||||||
|
9071.99.0547 (73_Z-0-0-547) |
230 ± 15% | 675 | 20 | 30 | 10-15 | 6x8 | |||||||||||||
|
9071.99.0548 (73_Z-0-0-548) |
90 ± 20% | 500 | 20 | 30 | 10-15 | 6x8 | |||||||||||||
|
9071.99.0549 (73_Z-0-0-549) |
350 ± 15% | 875 | 20 | 30 | 10-15 | 6x8 | |||||||||||||
|
9071.99.0550 (73_Z-0-0-550) |
470 ± 15% | 1000 | 20 | 30 | 10-15 | 6x8 | |||||||||||||
|
9071.99.0551 (73_Z-0-0-551) |
600 ± 15% | 1100 | 20 | 30 | 10-15 | 6x8 | |||||||||||||
For first selection and replacement of size 8x8 mm GDT
Suitable for the following installed GDT holder:

| H+S Type |
UZstat (V) |
UZdyn (V) |
IS 8/20 µs (kA) |
ISG 8/20 µs (kA) |
UARC (V) |
Dim. (mm) |
|||||||||||||
|
9071.99.0447 (73_Z-0-0-447) |
230 ± 15% | 675 | 20 | 30 | 10-15 | (8x8)* | |||||||||||||
|
9071.99.0448 (73_Z-0-0-448) |
90 ± 20% | 500 | 20 | 30 | 10-15 | (8x8)* | |||||||||||||
|
9071.99.0449 (73_Z-0-0-449) |
350 ± 15% | 875 | 20 | 30 | 10-15 | 8x8 | |||||||||||||
|
9071.99.0450 (73_Z-0-0-450) |
470 ± 15% | 1000 | 20 | 30 | 10-15 | (8x8)* | |||||||||||||
|
9071.99.0451 (73_Z-0-0-451) |
600 ± 15% | 1100 | 20 | 30 | 10-15 | (8x8)* | |||||||||||||
*6x8 mm GDT of the first table together with new GDT holder with grove
Ionized GDT - Phase out!
Alternative for first selection and replacement of size 8x8 mm GDT
Suitable for the following installed GDT holder:

| H+S Type |
UZstat (V) |
UZdyn (V) |
IS 8/20 µs (kA) |
ISG 8/20 µs (kA) |
UARC (V) |
Dim. (mm) |
|||||||||||||
|
9071.99.0047 (73_Z-0-0-47) |
230 ± 15% | 750 | 20 | 40 | 10 - 20 | 8x8 | |||||||||||||
|
9071.99.0049 (73_Z-0-0-49) |
350 ± 15% | 950 | 20 | 40 | 10 - 20 | 8x8 | |||||||||||||
|
9071.99.0050 (73_Z-0-0-50) |
470 ± 15% | 1400 | 20 | 40 | 10 - 20 | 8x8 | |||||||||||||
|
9071.99.0052 (73_Z-0-0-52) |
900 ± 15% | 2000 | 20 | 40 | 10 - 20 | 8x8 | |||||||||||||
|
9071.99.0053 (73_Z-0-0-53) |
1200 ± 15% | 2500 | 15 | 30 | 10 - 20 | 8x8 | |||||||||||||
|
9071.99.0054 (73_Z-0-0-54) |
1500 ± 15% | 3500 | 15 | 30 | 10 - 20 | 8x8 | |||||||||||||
Notes:
-GDT activity 0.2 MBq max.
Definitions
UZstat
Static spark-over voltage – voltage which ignites the GDT in the case of a voltage rise of less than 100 V/ms.
UZdyn
Dynamic spark-over voltage – voltage which ignites the GDT in the case of a voltage rise of 1 kV/ µs.
IS
Impulse discharge current – peak value of a defined current pulse which is allowed to be applied at least ten times at intervals of 30 seconds without causing any significant changes of the spark-over voltage specification. Values are given for current pulse shape definitions of 8/20 µs (rise time/half-value period).
ISG
Maximum pulse current – peak value of a defined single current pulse which can be conducted to ground without mechanical destruction or restriction of the protection function. For pulse shape refer to IS.
UARC
Arc voltage – increasing current drives the GDT into the arc state. The resulting voltage across the GDT is the arc voltage.
Concerning the selection of a suitable GDT, refer to section «Selection of gas discharge tubes».